- Density Test Report Report ID: 74717
- Edit Download Report
Density Test Report
Date :12/19/2024
Project No :2024C168
Client Company :CCG
Arrival Time :12/19/2024 8:00
Onsite Hours :9:45
Name of the Project :Reserve @ Gum Springs
Project Location :Jefferson
Weather :sunny
Departure Time :12/19/2024 17:45
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
12/19/2024 | 385 | 25.2 | 98.1 | 26081 | 102.9 | 20.0 | 95.3 | 95 | D2937 | Pass |
Location : | water line in the front of lot#226, Elv/Depth :1 foot below finish grade | |||||||||
Comment : | moisture content was high than specified Moisture content limit | |||||||||
12/19/2024 | 386 | 28.2 | 91.6 | 26082 | 94.1 | 24.3 | 97.3 | 95 | D2937 | Pass |
Location : | water line in the front of lot#228, Elv/Depth :2 feet below finish grade | |||||||||
Comment : | moisture content was high than specified Moisture content limit | |||||||||
12/19/2024 | 387 | 22.4 | 98.6 | 26081 | 102.9 | 20.0 | 95.8 | 95 | D2937 | Pass |
Location : | water line in the front of lot#230, Elv/Depth :1.5 feet below finish grade | |||||||||
Comment : | ||||||||||
12/19/2024 | 388 | 21.5 | 101.0 | 26081 | 102.9 | 20.0 | 98.2 | 95 | D2937 | Pass |
Location : | water line in the front of lot#232, Elv/Depth :finished grade | |||||||||
Comment : | ||||||||||
12/19/2024 | 389 | 28.4 | 90.0 | 26082 | 94.1 | 24.3 | 95.6 | 95 | D2937 | Pass |
Location : | water line in the front of lot#229, Elv/Depth :finish grade | |||||||||
Comment : | moisture content was high than specified Moisture content limit | |||||||||
12/19/2024 | 390 | 23.4 | 97.9 | 26081 | 102.9 | 20.0 | 95.1 | 95 | D2937 | Pass |
Location : | water line in the front of lot#224, Elv/Depth :finished grade | |||||||||
Comment : | ||||||||||
12/19/2024 | 391 | 22.4 | 98.0 | 26081 | 102.9 | 20.0 | 95.2 | 95 | D2937 | Pass |
Location : | water line in the front of lot#226, Elv/Depth :finished grade | |||||||||
Comment : |
Technician Signature / DateAminullah Azimi, December 19, 2024