- Density Test Report Report ID: 73998
- Edit Download Report
Density Test Report
Date :12/06/2024
Project No :2024C202
Client Company :CCG
Arrival Time :12/06/2024 07:15
Onsite Hours :
Name of the Project :Old Griffin Rd - Hawthorne Reserve
Project Location :Dallas
Weather :Sunny
Departure Time :
ASEC Technician Name :Solomon Cherie
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
12/13/2024 | 136 | 27.2 | 88.7 | S-02 | 97.2 | 24.9 | 91.3 | 95 | D6938 | Fail |
Location : | Lot#114, Elv/Depth :-2.5 | |||||||||
Comment : | The moisture is in agreement with the proctor but compaction is below 95%. This is informed to the superintendent to take action. | Gauge Serial No. :30942 |
Technician Signature / DateSolomon Cherie, December 6, 2024