Density Test Report

Date :05/24/2024
Project No :2024C112
Client Company :SR Homes
Arrival Time :05/24/2024 11:30
Onsite Hours :05:00
Name of the Project :Sterlington
Project Location :Canton
Weather :cloudy
Departure Time :05/24/2024 16:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/24/2024 1 15.2 99.5 P-02 105.9 18.8 94.0 95 D6938 Fail
Location : Lot #13, Elv/Depth :finished grade
Comment : Gauge Serial No. :38069
05/24/2024 2 16.2 99.2 P-02 105.9 18.8 93.7 95 D6938 Fail
Location : Lot #14, Elv/Depth :finished grade
Comment : Gauge Serial No. :38069
05/24/2024 3 17.9 99.6 P-02 105.9 18.8 94.1 95 D6938 Fail
Location : basement of Lot #15, Elv/Depth :4 feet below from basement finished grade
Comment : Gauge Serial No. :38069
05/24/2024 4 17.1 99.2 P-02 105.9 18.8 93.7 95 D6938 Fail
Location : basement of Lot #16, Elv/Depth :2 feet below from basement finished grade
Comment : Gauge Serial No. :38069
Technician Signature / DateAminullah Azimi, May 24, 2024
Reviewer Name / DateKenneth Mosman, July 15, 2024