- Density Test Report Report ID: 65662
- Edit Download Report
Density Test Report
Date :04/02/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :04/02/2024 08:30
Onsite Hours :07:15
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :Cloudy
Departure Time :04/02/2024 15:45
ASEC Technician Name :Fawad Shagiwal
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
04/02/2024 | 01 | 25.2 | 88.7 | 1 | 83.2 | 25.3 | 106.6 | 95 | D6938 | Pass |
Location : | Lot #26, Elv/Depth :12 feet from the bottom of the MSE wall | |||||||||
Comment : | Gauge Serial No. :3430 | |||||||||
04/02/2024 | 02 | 24.1 | 87.2 | 1 | 83.2 | 25.3 | 104.8 | 95 | D6938 | Pass |
Location : | Lot #28, Elv/Depth :12 feet from the bottom of the MSE wall | |||||||||
Comment : | Gauge Serial No. :3430 |
Technician Signature / DateFawad Shagiwal, April 2, 2024
Reviewer Name / DateKenneth Mosman, April 25, 2024