- Density Test Report Report ID: 64283
- This project is inactive from admin.Download Report
Density Test Report
Date :02/19/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/19/2024 12:00
Onsite Hours :03:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/19/2024 15:30
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
02/19/2024 | 1 | 14.3 | 101.7 | 24469 | 103.9 | 18.7 | 97.9 | 95 | D6938 | Pass |
Location : | Lot #32, Elv/Depth :3 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
02/19/2024 | 2 | 14.6 | 121.1 | 24468 | 111.3 | 17.5 | 95.0 | 95 | D6938 | Fail |
Location : | Lot #25, Elv/Depth :1 foot below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
02/19/2024 | 3 | 16.6 | 123.3 | 24468 | 111.3 | 17.5 | 95.0 | 95 | D6938 | Fail |
Location : | Lot #26, Elv/Depth :1 foot below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, February 19, 2024
Reviewer Name / DateKenneth Mosman, March 13, 2024