Density Test Report

Date :02/17/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :02/17/2024 8:30
Onsite Hours :04:30
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :sunny
Departure Time :02/17/2024 13:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/17/2024 1 30 91.5 2 95.0 23.5 96.3 95 D6938 Pass
Location : Lot #24, Elv/Depth :3.5 feet below finished grade
Comment : Moisture content over 3 percent over optimum moisture Gauge Serial No. :85759
02/17/2024 2 24.3 85.6 1 83.2 25.3 102.9 95 D6938 Pass
Location : Basement for Lot #24, Elv/Depth :2 feet below finished grade
Comment : Gauge Serial No. :85759
02/17/2024 3 30.3 87.0 2 95.0 23.5 91.6 95 D6938 Fail
Location : Lot #25, Elv/Depth :2 feet below finished grade
Comment : Moisture content exceeds 3 percent over optimum moisture content Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 17, 2024
Reviewer Name / DateKenneth Mosman, March 13, 2024