- Density Test Report Report ID: 63875
- This project is inactive from admin.Download Report
Density Test Report
Date :01/31/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :01/31/2024 10:00
Onsite Hours :06:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :01/31/2024 16:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
01/31/2024 | 1 | 15.7 | 103.4 | 24468 | 111.3 | 17.5 | 92.9 | 90 | D6938 | Pass |
Location : | Creek crossing (location shown in pictures), Elv/Depth :12 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/31/2024 | 2 | 15.7 | 103.4 | 24468 | 111.3 | 17.5 | 92.9 | 90 | D6938 | Pass |
Location : | Creek crossing (location shown in pictures), Elv/Depth :13 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/31/2024 | 2 | 17.1 | 105.7 | 24468 | 111.3 | 17.5 | 95.0 | 90 | D6938 | Pass |
Location : | Creek crossing (location shown in pictures) , Elv/Depth :12 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/31/2024 | 3 | 16.6 | 103.6 | 24468 | 111.3 | 17.5 | 93.1 | 90 | D6938 | Pass |
Location : | Creek crossing(location shown in pictures), Elv/Depth :11 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/31/2024 | 4 | 15.9 | 103.5 | 24468 | 111.3 | 17.5 | 93.0 | 90 | D6938 | Pass |
Location : | Creek crossing (location shown in pictures), Elv/Depth :11 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, January 31, 2024
Reviewer Name / DateKenneth Mosman, March 10, 2024