- Home
- Density Test Report Report ID: 63443
- This project is inactive from admin.Download Report
Density Test Report
Date :12/19/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/19/2023 12:00
Onsite Hours :04:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/19/2023 16:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
12/19/2023 | 1 | 14.9 | 102.7 | 24468 | 111.3 | 17.5 | 92.3 | 90 | D6938 | Pass |
Location : | Lot #32, Elv/Depth :8 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
12/19/2023 | 2 | 17.5 | 101.1 | 24468 | 111.3 | 17.5 | 90.8 | 90 | D6938 | Pass |
Location : | Roadway in the front of Lot #32., Elv/Depth :6.5 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, December 19, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024