Density Test Report

Date :05/18/2023
Project No :2022C113
Client Company :CWM
Arrival Time :05/18/2023 7:30
Onsite Hours :06:00
Name of the Project :Airfield Sewer Enhancements
Project Location :HJAIA
Weather :cloudy
Departure Time :05/18/2023 13:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
05/18/2023 1 7.1 133.6 GAB 23411 140.2 5.7 95.3 90 D6938 Pass
Location : 33 feet to North of MH2, Elv/Depth :6 inches below finish grade
Comment : test result on standby for proctor Gauge Serial No. :85759
05/18/2023 2 7.1 133.1 GAB 23411 140.2 5.7 94.9 90 D6938 Pass
Location : 43 feet to South of MH3, Elv/Depth :6 inches below finish grade
Comment : test result standby for proctor Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, May 18, 2023
Reviewer Name / DateRamchandra Mogulla, July 10, 2023