Density Test Report
Date :06/11/2024
Project No :2024C112
Client Company :SR Homes
Arrival Time :06/11/2024 9:00
Onsite Hours :08:00
Name of the Project :Sterlington
Project Location :Canton
Weather :sunny
Departure Time :06/11/2024 17:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
06/11/2024 | 1 | 15.6 | 99.3 | P-02 | 105.9 | 18.8 | 93.8 | 95 | D6938 | Fail |
Location : | Lot #18, Elv/Depth :2 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :38069 | |||||||||
06/11/2024 | 2 | 15.7 | 98.7 | P-02 | 105.9 | 18.8 | 93.2 | 95 | D6938 | Fail |
Location : | Lot #19, Elv/Depth :6 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :38069 |
Technician Signature / DateAminullah Azimi, June 11, 2024
Reviewer Name / DateKenneth Mosman, July 19, 2024