Density Test Report

Date :06/04/2024
Project No :2024C112
Client Company :SR Homes
Arrival Time :06/04/2024 9:00
Onsite Hours :08:00
Name of the Project :Sterlington
Project Location :Canton
Weather :sunny
Departure Time :06/04/2024 17:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
06/04/2024 1 17.2 99.2 P-02 105.9 18.8 93.7 95 D6938 Fail
Location : Lot #8, basement , Elv/Depth :basement finished grade
Comment : Gauge Serial No. :38069
06/04/2024 2 15.7 100.2 P-02 105.9 18.8 94.6 95 D6938 Fail
Location : Lot #8, Elv/Depth :4 feet below finished grade
Comment : Gauge Serial No. :38069
06/04/2024 3 17.3 99.5 P-02 105.9 18.8 94.0 95 D6938 Fail
Location : Lot #7, basement , Elv/Depth :1.5 feet below from basement finished grade
Comment : Gauge Serial No. :38069
06/04/2024 4 15.5 96.0 P-02 105.9 18.8 90.7 95 D6938 Fail
Location : Lot #7, basement , Elv/Depth :basement finished grade
Comment : Gauge Serial No. :38069
06/04/2024 5 15.2 99.0 P-02 105.9 18.8 93.5 95 D6938 Fail
Location : Lot #8, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :38069
Technician Signature / DateAminullah Azimi, June 4, 2024
Reviewer Name / DateKenneth Mosman, July 16, 2024