Density Test Report

Date :06/30/2024
Project No :2024C112
Client Company :SR Homes
Arrival Time :06/30/2024 12:30
Onsite Hours :06:00
Name of the Project :Sterlington
Project Location :Canton
Weather :sunny
Departure Time :06/30/2024 18:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
06/30/2024 1 17.7 99.4 P-02 105.9 18.8 93.9 95 D6938 Fail
Location : Lot #8, Elv/Depth :7 feet below finished grade
Comment : Gauge Serial No. :38069
06/30/2024 2 16 95.4 P-02 105.9 18.8 90.1 95 D6938 Fail
Location : Lot #8, basement, Elv/Depth :5 feet below finished grade
Comment : Gauge Serial No. :38069
06/30/2024 3 18.9 100.5 P-02 105.9 18.8 94.9 95 D6938 Fail
Location : Lot #8, Elv/Depth :6 feet below finished grade
Comment : Gauge Serial No. :38069
06/30/2024 4 15.7 99.0 P-02 105.9 18.8 93.5 95 D6938 Fail
Location : Lot #8, basement, Elv/Depth :4.5 feet below finished grade
Comment : Gauge Serial No. :38069
06/30/2024 5 18.9 100.0 P-02 105.9 18.8 94.4 95 D6938 Fail
Location : Lot #8, Elv/Depth :5.5 feet below finished grade
Comment : Gauge Serial No. :38069
Technician Signature / DateAminullah Azimi, June 30, 2024
Reviewer Name / DateKenneth Mosman, July 25, 2024