- Density Test Report Report ID: 65634
- Edit Download Report
Density Test Report
Date :04/01/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :04/01/2024 08:30
Onsite Hours :07:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :Cloudy
Departure Time :04/01/2024 15:30
ASEC Technician Name :Fawad Shagiwal
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
04/01/2024 | 01 | 23.5 | 96.7 | 2 | 95.0 | 23.5 | 101.8 | 95 | D6938 | Pass |
Location : | Lot #26, Elv/Depth :9 Feet from the bottom of the MSE wall | |||||||||
Comment : | Gauge Serial No. :3430 | |||||||||
04/01/2024 | 02 | 22.6 | 90.2 | 5 | 93.8 | 20.9 | 96.2 | 95 | D6938 | Pass |
Location : | Lot #28, Elv/Depth :9 feet from the bottom of the MSE wall | |||||||||
Comment : | Gauge Serial No. :3430 |
Technician Signature / DateFawad Shagiwal, April 1, 2024
Reviewer Name / DateKenneth Mosman, April 25, 2024