Density Test Report

Date :03/13/2024
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :03/13/2024 13:00
Onsite Hours :04:00
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :sunny
Departure Time :03/13/2024 17:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
03/13/2024 1 23.4 97.8 3 99.4 21.3 98.4 95 D6938 Pass
Location : Lot #18, basement , Elv/Depth :finished grade
Comment : Gauge Serial No. :85759
03/13/2024 2 23.1 118.1 3 99.4 21.3 96.5 95 D6938 Pass
Location : Lot #19, basement , Elv/Depth :finished grade
Comment : Gauge Serial No. :85759
03/13/2024 3 26.4 92.3 5 93.8 20.9 98.4 95 D6938 Pass
Location : Lot #20, basement , Elv/Depth :finished grade
Comment : Moisture content more than 3 percent over optimum moisture content Gauge Serial No. :85759
03/13/2024 4 25.8 89.7 4 98.6 20.2 91.0 90 D6938 Pass
Location : 71 feet SE of SSMH A5, Elv/Depth :2 feet below finished grade
Comment : Moisture content more than 3 percent over optimum moisture content Gauge Serial No. :85759
03/13/2024 5 24.5 91.4 4 98.6 20.2 92.7 90 D6938 Pass
Location : 73 feet NW of SSMH A6, Elv/Depth :7 feet below finished grade
Comment : Moisture content more than 3 percent over optimum moisture content Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, March 13, 2024
Reviewer Name / DateKenneth Mosman, March 28, 2024