Density Test Report

Date :02/19/2024
Project No :2023C141
Client Company :Toll Bros
Arrival Time :02/19/2024 12:00
Onsite Hours :03:30
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :02/19/2024 15:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
02/19/2024 1 14.3 101.7 24469 103.9 18.7 97.9 95 D6938 Pass
Location : Lot #32, Elv/Depth :3 feet below finished grade
Comment : Gauge Serial No. :85759
02/19/2024 2 14.6 121.1 24468 111.3 17.5 95.0 95 D6938 Fail
Location : Lot #25, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
02/19/2024 3 16.6 123.3 24468 111.3 17.5 95.0 95 D6938 Fail
Location : Lot #26, Elv/Depth :1 foot below finished grade
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, February 19, 2024
Reviewer Name / DateKenneth Mosman, March 13, 2024