- Density Test Report Report ID: 63652
- This project is inactive from admin.Download Report
Density Test Report
Date :01/05/2024
Project No :2023C195
Client Company :Toll Bros. Inc.
Arrival Time :01/05/2024 11:00
Onsite Hours :05:00
Name of the Project :Kimbal Bridge Tract
Project Location :Alpharetta
Weather :sunny
Departure Time :01/05/2024 16:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
01/05/2024 | 1 | 16.3 | 123.5 | 24209 | 111.6 | 16.5 | 95.2 | 95 | D6938 | Pass |
Location : | Roadway (location shown in the picture), Elv/Depth :1 foot below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
01/05/2024 | 2 | 17.9 | 125.0 | 24209 | 111.6 | 16.5 | 95.0 | 95 | D6938 | Fail |
Location : | Water line, in the front of Lot #35, Elv/Depth :3 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, January 5, 2024
Reviewer Name / DateKenneth Mosman, March 10, 2024