- Density Test Report Report ID: 63394
- This project is inactive from admin.Download Report
Density Test Report
Date :12/18/2023
Project No :2023C141
Client Company :Toll Bros
Arrival Time :12/18/2023 9:00
Onsite Hours :03:00
Name of the Project :N. Gate - Old Atlanta Road
Project Location :Cumming
Weather :sunny
Departure Time :12/18/2023 12:00
ASEC Technician Name :Aminullah Azimi
Observations/Finding
Test Date | Test Number | Moisture Content (%) | Dry Density (pcf) | Proctor Number | Max. Dry Density (pcf) | Optimum Moisture (%) | Compaction (%) | Specified Compaction (%) | ASTM Test Method | Pass/Fail |
---|---|---|---|---|---|---|---|---|---|---|
12/18/2023 | 1 | 15.7 | 104.6 | 24468 | 111.3 | 17.5 | 94.0 | 90 | D6938 | Pass |
Location : | Lot #36, Elv/Depth :5 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
12/18/2023 | 2 | 15.8 | 100.3 | 24468 | 111.3 | 17.5 | 90.1 | 90 | D6938 | Pass |
Location : | Lot #37, Elv/Depth :2 feet below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 | |||||||||
12/18/2023 | 3 | 15.7 | 116.2 | 24468 | 111.3 | 17.5 | 90.2 | 90 | D6938 | Pass |
Location : | Lot #38, Elv/Depth :1.5 foot below finished grade | |||||||||
Comment : | Gauge Serial No. :85759 |
Technician Signature / DateAminullah Azimi, December 18, 2023
Reviewer Name / DateKenneth Mosman, March 09, 2024