Density Test Report

Date :04/25/2023
Project No :2022C165
Client Company :Toll Bros. Inc.
Arrival Time :04/25/2023 9:30
Onsite Hours :06:30
Name of the Project :Northfield @ Polo Fields - Phase2
Project Location :Pittman Road, Cumming, GA
Weather :cloudy
Departure Time :04/25/2023 16:00
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
04/25/2023 1 30.1 91.6 3 99.4 21.3 92.2 90 D6938 Pass
Location : 110 feet to NW of MH BB12, Elv/Depth :2 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/25/2023 2 28 92.3 3 99.4 21.3 92.9 90 D6938 Pass
Location : 10 feet to NW of MH BB11, Elv/Depth :2 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/25/2023 3 30.1 91.5 3 99.4 21.3 92.1 90 D6938 Pass
Location : Between MH BB10 and MHBB11, Elv/Depth :2 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/25/2023 4 28.8 89.8 3 99.4 21.3 90.3 90 D6938 Pass
Location : 78 feet to NW of MHBB12, Elv/Depth :2.5 below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
04/25/2023 5 29.6 91.4 3 99.4 21.3 92.0 90 D6938 Pass
Location : 39 feet to NW of MH BB12 , Elv/Depth :2 feet below finished grade
Comment : Moisture exceeded from specific limit range. Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, April 25, 2023
Reviewer Name / DateKenneth Mosman, May 07, 2023