- Concrete Test Report Report ID: 57390
- Edit Download Report
Concrete Test Report
Date :03/02/2023
Project No :2023C111
Client Company :2MATL
Arrival Time :03/02/2023 8:30
Onsite Hours :06:00
Name of the Project :DOA Fiber Infrastructure Improvements
Project Location :HJAIA
Weather :cloudy
Departure Time :03/02/2023 14:30
ASEC Technician Name :Aminullah Azimi
Concrete Placement Information
Location(S):
Testing:
1 Set of concrete specimens (6 Cylinders per set) were cast during the cast-in-place concrete pour at the above referenced location, in accordance with ASTM C31. The cylinders will remain on site for the initial 24-48 hrs curing.
Compliance:
Field placement of concrete appeared to be in accordance with the project specifications (i.e., slump, temperature, etc) (refer to remarks below)
Deviations and/or noncompliances were noted during the field placement (refer to remarks below)
Cylinders
Pick Up: 1 Sets of concrete cylinders/ 6 cylinders per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Pick Up: 1 Sets of concrete cylinders/ 6 cylinders per set were picked up & transported to AS Engineering and Consulting LLC (ASEC) for curing and testing in accordance with ASTM C39, C670/1231
Field Curing:
Cylinders were stored for the initial 24 hours
Near the poured structure
In an insulated curing box
Other
Remarks:
Field Test Data
Set Number :1
Date Sampled :03/02/2023
Sampled By :Aminullah Azimi
Contractor :BBH
Truck Number :1449
Time Batched :9:16
Location of Placement :100 feet to west from DOA-A3D
Number of samples cast :6
Ambient Temperature (°f) :60
Slump (in.) :6
Water added (gal.) :0
Laboratory Number :6
Time Sampled :10:40
Weather Condition :cloudy
Concrete Supplier :WDC
Mix ID :626
Quantity of Load (cu. yd.) :10
Sample Cast :1
Specified Strength :3000
Concrete Temperature(°f) :75
Air Content (%) :6.9
Strength Test Results
Specimen Number | Age (days) | Date Tested | Dia(in.) | Area (sq in.) | Maximum Loads (lbs) | Strength (lbs) | % Design Strength | Type of Fracture |
---|---|---|---|---|---|---|---|---|
1 | 7 | 03/09/2023 | ||||||
2 | 7 | 03/09/2023 | ||||||
3 | 27.958333333333332 | 03/30/2023 | ||||||
4 | 27.958333333333332 | 03/30/2023 | ||||||
5 | ||||||||
6 |
UNLESS OTHERWISE SPECIFIED, TESTS WERE PERFORMED IN ACCORDANCE WITH ASTM TEST METHODS C31, C39, C138, C143, C173, AND C1064. FRACTURE TYPE INDICATED BY NUMBER.
(Type 1) Cone (Type 2) Cone-split (Type 3) Vertical (Type 4) Shear (Type 5) Edge Fracture (Type 6) Pointed
Technician Signature / DateAminullah Azimi, March 2, 2023
Reviewer Name / DateKenneth Mosman, March 14, 2023