Density Test Report

Date :09/27/2022
Project No :2022C135
Client Company :Mark Spain
Arrival Time :09/27/2022 9:00
Onsite Hours :06:30
Name of the Project : Barnett Shoals Road Development
Project Location :Watkinsville
Weather :sunny
Departure Time :09/27/2022 15:30
ASEC Technician Name :Aminullah Azimi

Observations/Finding

Test Date Test Number Moisture Content (%) Dry Density (pcf) Proctor Number Max. Dry Density (pcf) Optimum Moisture (%) Compaction (%) Specified Compaction (%) ASTM Test Method Pass/Fail
09/27/2022 1 22.1 103.4 P-2 99.5 22.1 103.9 95 D6938 Pass
Location : 32 feet to the North of keyway and 111 feet away from Dam west side of the dam starting point, Elv/Depth :-17 from the top of the dam
Comment : Upon arrival work was already in progress contractor were placing lifts, each lift being 6-8 inches in thickness. Gauge Serial No. :85759
09/27/2022 2 23.5 100.0 P-2 99.5 22.1 100.5 95 D6938 Pass
Location : 26 feet to the south side of keyway and 101 feet from west side starting point of the dam, Elv/Depth :-19 from the top of the dam
Comment : Gauge Serial No. :85759
Technician Signature / DateAminullah Azimi, September 27, 2022
Reviewer Name / DateKenneth Mosman, October 23, 2022