Daily Field Report

Date :01/09/2022
Project No :2021C060
Client Company :Pulte Group
Arrival Time :01/07/2022 02:30
Onsite Hours :02:30
Name of the Project :Suncity - Peachtree
Project Location :Griffin, GA
Weather :Sunny
Departure Time :01/07/2022 05:00
ASEC Technician Name :Russell Hendrix

Observations/Finding

DCP TEST DATA SHEET
                         
Project Name: Suncity   Date: Jan 7,2022
Project Number: 2021C060   Technician: Russ Hendrix
Project Location: Griffin, GA
     
                         
DCP LOCATION:
Lot #8, North/South/Center 
etc.
Back/Side of lot footing   DCP LOCATION:
Lot #, North/South/Center etc
 
     
                         
Depth
(feet)
Set
2″
N
1.75″
Description   Depth
(feet)
Set
2″
N
1.75″
Description
1 3 Red medium sandy silt   1      
2   3 Red medium sandy silt   2      
3   10 Red medium sandy silt   3      
4   13 Red medium sandy silt   4      

The site was visited by the undersigned AS Engineering and Consulting (ASEC) representative for the purpose of providing quality control inspection and testing services. Visual observation techniques were employed to assure compliance with project drawings/specifications, applicable codes, and materials submittals.  Our observations were specifically for the proposed home on Lot #8. 

Upon arrival it was observed that rebar and plastic barriers were placed in accordance with job specifications for size, spacing and quantity.  It appears the back side of the proposed home will sit on 10 to 15 feet of fill.

It was noted that a section of the footing 25 feet from the right corner of the home adjacent to the road (as viewed from the adjacent road) and another 10 feet along the back of the home from the right corner (a total of 35 linear feet) probed soft between depths of 8 to 16 inches.  A DCP was conducted in this soft area (see attached table for results).  After consultation with Mr. Ram Mogulla, Professional Engineer with AS Engineering and Consulting (ASEC) it was determined that this section of the footing would need to be undercut 12 inches to remove these soft materials and replaced with 12 inches of #57 stone.  Please see attached drawing (footing remediation is highlighted) for the specific footing location.  This location (35 linear feet) was also marked at the site.

Please see attached drawing.

 

Technician Signature / DateRussell Hendrix, January 9, 2022
Reviewer Name / DateKenneth Mosman, January 09, 2022